Input Power | Control: 18-30 VAC 50/60 Hz (Class 2 Transformer) |
Input Current Drain | 300 mA @24 VAC with gas and pilot relays energized (Control only) |
Main Gas Valve | 2.0A max (continuous) |
Pilot Gas Valve | 2.0A max (continuous) |
Operating Temperature | -40 to +176 deg. F (-40 to +80 deg. C) |
Sforage Temperature | -40 deg. F to +185 deg. F (-40 deg. C to +85 deg. C) |
Flame Sensitivity | 0.3 uA minimum |
Flame Failure Response or Re-ignition Time | 0.8 seconds maximum |
Flame Detecfor Self-check Rate | Once per second minimum |
Types of Gas | Natural, LP, or manufactured |
Spark Rate | Remote sense (50/60 Hz) Local sense (25/30 Hz) |
Size (LxWXH) | 4.92 x 3.32 x 2.71 inches (with cover) 12.50 x 8.43 x 6.88 cm (with cover) |
Weight | 8 ounces (nominal) 224 grams (nominal) |
Moisture Resistance | Conformal coated to operate to 95% R.H. (non-condensing) |
Tries for Ignition | One or three try versions available |
Trial for Ignition Periods | 8, 25, 50, 85, 120 seconds available |
Prepurge Timings | None, 4, 15, or 30 seconds available |
Interpurge Timings | None, 15, 30, or 45 seconds available |